FLUKE 1630-2 FC Газардуулгын эсэргүүцэл хэмжигч

  • үнэ: 10,200,000 төг

Earth ground ac leakage current measurement

Identify ac leakage currents without disconnecting the earth ground stake from the grounding system–ideal for system troubleshooting.

Rugged

Heavy-duty clamp jaw stays in alignment and in calibration even in every day, on-the-job industrial environments.

Logging measurements

The earth ground clamp saves time by automatically recording data at pre-set intervals and saves up to 32,760 measurements in memory at the set logging interval. Saves time by recording and storing measured values.

Alarm threshold

User-defined high/low alarm limits, for rapid measurement evaluation.

Band-pass filter

Selectable band-pass filter function removes unwanted noise from the ac leakage current measurement.

Key features

Test the grounding components of equipment in hard-to-reach spaces, including areas that are indoors or fully paved and do not permit driving auxiliary test stakes. Stay on line—identify ground loop resistance without the need to disconnect then reconnect the earth electrode from the system.

The Fluke 1630-2 FC Stakeless Earth Ground Clamp is the kind of high-quality, rugged tool you expect from Fluke. Heavy-duty clamp jaw stays in alignment and in calibration even in every day, on-the-job industrial environments.

Stakeless measurement

The 1630-2 FC clamp measures earth ground loop resistances for multi-grounded systems using the dual-clamp jaw. This test technique eliminates the dangerous and time-consuming activity of disconnecting parallel grounds, as well as the process of finding suitable locations for auxiliary test stakes. You can also perform ground tests in places that were previously difficult: inside buildings, on power pylons or anywhere you don’t have access to soil to place auxiliary test stakes.

Fluke Connect® Wireless System

The 1630-2 FC supports the Fluke Connect Wireless System (may not be available in all regions). Fluke Connect wirelessly connects the clamp with an app on your smartphone or tablet. The app shows the ground resistance measurements on your smartphone or tablet display. You can save these measurements, GPS location from your phone and images to Fluke Connect Cloud storage and share with your team.


Specifications: Fluke 1630-2 FC Earth Ground Clamp

Electrical Specifications
Maximum voltage to earth ground 1000 V
Battery type AA alkaline IEC/EN LR6 (x4)
Battery life More than 15 hours*
* In Ground Resistance measurement mode, with backlight turned off, and RF mode turned off
Frequency range 40 Hz to 1 kHz
Ingress protection IEC/EN 60529: IP30 with jaw closed
LCD Digital reading 9999 counts
Refresh rate 4 per second
Operating temperature -10 °C to + 50 °C
Storage temperature -20 °C to + 60 °C
Operating humidity Non condensing (<10 °C) (< 50 °F)
≤90% RH (at 10 °C to 30 °C [50 °F to 86 °F])
≤75% RH (at 30 °C to 40 °C [86 °F to 104 °F])
≤45% RH (at 40 °C to 50 °C [104 °F to 122 °F])
(Non condensing)
Operating altitude 2000 m (6561 feet)
Storage altitude 12 000 m (39,370 feet)
Reference temperature 23 °C ±5 °C (73 °F ±9 °F)
Temperature coefficient 0.15% x (specified accuracy)/ °C (<18 °C or >28 °C [<64.4 °F or >82.4 °F])
Overload indication OL
Data logging capacity Minimum of 32,760 measurements
Data logging interval 1 second to 59 minutes and 59 seconds
Display reading specification with standard loop resistance
Input (Ω) Minimum Maximum
0.474 0.417 0.531
0.5 0.443 0.558
10 9.55 10.45
100 96 104
Safety
General IEC/EN 61010-1: Pollution Degree 2 IEC/EN 61557-1
Measurement IEC/EN 61010-2-032: CAT IV 600 V / CAT III 1000 V
Current clamp for leakage current measurements IEC/EN 61557-13: Class 2, ≤30 A/m
Resistance to earth IEC/EN 61557-5
Effectiveness of thepProtective measures IEC/EN 61557-16
Electromagnetic compatibility (EMC) International IEC/EN 61326-1: Portable Electromagnetic Environment
CISPR 11: Group 1, Class B, IEC/EN 61326-2-2
Korea (KCC) Class A equipment (Industrial Broadcast & Communications Equipment)
USA (FCC) 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Wireless Radio
Frequency range 2412 MHz to 2462 MHz
Output power <10 mW
Radio frequency certification FCC ID:T68-FBLE IC:6627A-FBLE
General Specifications
Conductor size 40 mm (1.57 in) approximately
Dimensions (L x W x H) 283 x 105 x 48 mm (11.1 x 4.1 x 1.9 in)
Weight 880g (31 oz)
Warranty One year
Earth Ground Loop Resistance
Range Accuracy1  ± (% of reading + Ω)
0.025 Ω to 0.249 Ω 1.5% + 0.02 Ω
0.250 Ω to 0.999 Ω 1.5% + 0.05 Ω
1.000 Ω to 9.999 Ω 1.5% + 0.10 Ω
10.00 Ω to 49.99 Ω 1.5% + 0.30 Ω
50.00 Ω to 99.99 Ω 1.5% + 0.50 Ω
100.0 Ω to 199.9 Ω 3.0% + 1.0 Ω
200.0 Ω to 399.9 Ω 5.0% + 5.0 Ω
400 Ω to 599 Ω 10.0% + 10 Ω
600 Ω to 1500 Ω 20.00%
1  Loop resistance with no inductance, conductor centered and perpendicular to jaw
Earth ground leakage current mA
Autorange 50/60 Hz, True rms, crest factor CF ≤3
Range Resolution Accuracy1  ± (% of reading + mA)
0.200 mA to 3.999 mA 1 μA 2.0% + 0.05 mA
4.00 mA to 39.99 mA 10 μA 2.0% + 0.03 mA
40.0 mA to 399.9 mA 100 μA 2.0% + 0.3 mA
0.400 A to 3.999 A 1 mA 2.0% + 3 mA
4.00 A to 39.99 A 10 mA 2.0% + 30 mA
1 Applies to signal frequency

  • 40 Hz to 1 kHz with filter set to OFF
  • 40 Hz to 70 Hz with filter se to ON